Product Features

    Ideal for solar power generation systems, UPS and battery testing Large current measuring applications in the fields of EV and HEV hybrid electric vehicles (CT9693) Wide-bandwidth DC to 10 kHz (CT9691), 20 kHz (CT9692) excellent frequency characteristics Applications in solar power generation, battery charge and discharge, and measuring the secondary side of inverters For observing waveforms in combination with oscilloscopes or HIOKI MEMORY HiCORDERs (use with the CT6590)

    The Hioki CT9691, CT9692 and CT9693 AC/DC clamp sensors are designed to meet new DC measurement needs. They're ideal for solar power generation systems, UPS and battery testing.

    Basic specifications (Accuracy guaranteed for 1 year, or opening and closing of the clamp sensor 10,000 times)

    CT9691 CT9692 CT9693
    Rated input current 100 A AC/DC 200 A AC/DC 2000 A AC/DC
    Max. allowable input Continuous 100 Arms Continuous 200 Arms Continuous 2000 Arms
    Band width DC to 10 kHz (-3dB) DC to 20 kHz (-3dB) DC to 15 kHz (-3dB)
    Max. rated voltage to earth 600V AC/DC CAT III
    Power consumption 50 mVA
    Core diameter φ 35 mm (1.38 in) φ 33 mm (1.30 in) φ 55 mm (2.17 in)
    Dimensions, mass 53 mm (2.09 in) W × 129 mm (5.08 in) H × 18 mm (0.71 in) D, 230 g (8.1 oz) 62 mm (2.44 in) W × 167 mm (6.57 in) H × 35 mm (1.38 in) D, 410 g (14.5 oz) 62 mm (2.44 in) W × 196 mm (7.72 in) H × 35 mm (1.38 in) D, 500 g (17.6 oz)
    Supplied accessories Instruction manual

    CT6590 Basic specifications (Power supply for sensor, Accuracy guaranteed for 1 year)

    Compatible sensor models CT9691, 9691
    (9691: Phase not defined)
    CT9692, 9692
    (9692: Phase not defined)
    CT9693, 9693
    (9693: Phase not defined)
    Output Selectable H range/ L range, BNC terminal
    Output (in combination with a sensor) 100 mV f.s./100A range
    100 mV f.s./10A range
    200 mV f.s./200A range
    200 mV f.s./20A range
    200 mV f.s./2000A range
    200 mV f.s./200A range
    Amplitude basic accuracy
    (in combination with a sensor)
    ±1.5 % rdg. ±1.0 % f.s.
    (DC ≤ f ≤ 66 Hz)
    ±1.5 % rdg. ±0.5 % f.s.
    (DC ≤ f ≤ 66 Hz)
    ±1.5 % rdg. ±0.5 % f.s.
    (45 ≤ f ≤ 66 Hz)
    Phase basic accuracy
    (in combination with a sensor)
    ±2 deg. (DC < f ≤ 66 Hz) ±2 deg. (DC < f ≤ 66 Hz) ±2 deg. (45 ≤ f ≤ 66 Hz)
    Power supply Two (2) LR6 (AA) alkaline batteries, Continuous use : 25 hr (Rated Power 1 VA), or AC adapter 9445-02/-03 (Rated Power 1.5 VA), or External power supply 5 to 15 VDC (Rated Power 1.5 VA)
    Dimensions, mass 36 mm (1.42 in)W × 120 mm (4.72 in)H × 34 mm (1.34 in) D, 165 g (5.8 oz) (including batteries), cord length 1 m (3.28 ft)
    Supplied accessories Two (2) LR6 (AA) alkaline batteries, Instruction manual, Connector cover

    Note: To use the CT9691/ CT9692/ CT9693 sensor with the HIOKI PW3198 POWER QUALITY ANALYZER or the HIOKI MEMORY HiCORDER series, it must be connected and powered via the SENSOR UNIT CT6590

    Note: The CT9691/ CT9692/ CT9693 sensor may also be used with the CLAMP ON AC/DC HiTESTER 3290/ 3290-10 (without the SENSOR UNIT CT6590)