Digital Transformer Turns Radiometer Model 8511
Specifications
VT / PT Ratio Range Auto-Ranging 0.8000:1 to 8000.0:1
VT / PT Accuracies
Ratio 0.8000 to 9.9999: ± 0.2 % of Reading
Ratio 10.000 to 999.99: ± 0.1 % of Reading
Ratio 1000.0 to 4999.9: ± 0.2 % of Reading
Ratio 5000.0 to 8000.0: ± 0.25 % of Reading
Excitation Current Up to 2 A
CT Ratio Range Auto-Ranging 0.8000 to 1000.0
CT Accuracy ± 0.5 % of Reading
Output Voltage (VT / PT) 30 V @ 64 Hz
Output Voltage (CT) 5 V @ 64 Hz
Display LCD 20 characters x 4 line display
Wide Ratio Range – Accurately measures transformer ratios up to 8000:1 for VT/PT mode and 1000:1 for CT mode
Advanced Low-Voltage Step-Down Measurement – Applies test current to the primary side windings, enhancing operator safety and enabling testing across a wider range of transformer types and sizes
Automatic Test Cycles – Quickly checks for lead reversal and open circuits with no manual balancing required
Built-in Continuity Testing – Detects open transformer windings quickly
Deviation Calculations – Compare measured values to stored nameplate data for instant pass/fail results
Large Storage Capacity – Save up to 9801 test results for easy recall and reporting
PC Connectivity – Transfer data, set nameplate values and control the instrument remotely with included DataView® software
Rugged and Portable – Lightweight, field-ready design with an IP53-rated protective case (with lid closed)
Flexible Power Options – Operates on NiMH batteries or 12 Vdc external supply. Batteries can be recharged through USB-C connector or 12 Vdc external supply.
User-Friendly Interface – Bright backlit 4-line display, intuitive navigation keys, and audible test alerts
Precision, Accuracy, and Confidence in Every Test
The DTR® 8511 is the next-generation digital transformer ratiometer, engineered to make transformer testing faster, safer, and more reliable than ever. Building on the proven performance of the DTR® 8510, this enhanced model introduces modern upgrades for the field—combining rugged portability with advanced measurement technology
How the DTR® 8511 Improves on the DTR® 8510
Improved Test Performance
Matches the same ratio and accuracy ranges as the 8510, but with improved test power. It delivers fixed test voltages (30 Vac for VT/PT, 5 V for CT), and uses a 64 Hz test frequency for a more accurate field simulation. Additional enhancements include advanced continuity checks and improved diagnostics.
Smarter Data Storage and Memory
Both models can store up to 99 objects with 99 tests each. With the older DTR® 8510, nameplate values can only be edited through DataView®. The DTR® 8511 improves flexibility by offering 10 fixed nameplate ratios plus one customizable ratio, editable directly from the instrument or via software. It also supports manual, automatic, or no-save testing modes for greater control and efficiency.
Larger, Brighter Display and Easier Navigation
Upgraded 4-line LCD with a 6-button keypad and audible alerts for clearer visibility and more intuitive use.
More Convenient Power Options
AA NiMH batteries or 12Vdc and charges via USB-C or 12 Vdc.
Designed for Field Technicians
No hand cranking. No calibration. No wasted time.
The DTR® 8511 was built for fast, accurate, and hassle-free testing of transformers (power, VT/PTs, and CTs). With its brighter display, ergonomic design, and built-in safety checks, you’ll have confidence in every result.
In The Box
Includes (6) internal rechargeable AA NiMH batteries
Extra large carrying bag
Set of (2) 15 ft test leads (primary and secondary) with (4) alligator clips (red/black)
6 ft USB Type-C to Type-C cable
USB Type-C wall power adapter
10 ft USB
Type-A to Type-C cable